Troubleshooting
Troubleshoot common occurrences following our step-by-step guides.
Overtemperature Alarm
- Heaters stuck on / See related section below for troubleshooting tips
- Exhaust set too low / Turn up exhaust blower or open exhaust dampers to increase draw
- Heater setpoint too high / See equipment manual for recommended maximum temperature
Blower Fault – No Pressure Detected
- Pressure sensor fault / Check for loose wiring / Replace sensor
- Blower drive belt broken / Check and replace as required
- Inlet or outlet blocked / Check filters / Clean if necessary
Conveyor not running
- Drive faulted / Check faults at HMI screen / Reset fault if present
- Conveyor fuse blown / Check that conveyor is not bound up / Replace fuse
- Belt or chain broken / Check for breaks and replace as needed
PLC screen not operating
- Improper electrical supply / Ensure 24VDC power supply into PLC / Check that Control Power Switch is ON
- Program frozen or corrupted / Restart PLC. If problem persists, reload program back onto PLC
- Control panel enclosure overheated / Check filters for clogs / Check fans & A/C units for functionality / Replace & clean as needed
Heaters stuck on
- SCR or SSR fused closed / Shut off system power and check SCR or SSR for continuity across load terminals. Replace as necessary.
- Improper signal sent to power controller / Check for DC voltage signal into power controller when program is not running. If present, check for crossed wires or damaged PLC I/O
The incorrect temperature is indicated
- Verify that the thermocouple is properly positioned.
- If temperature is indicated but lower than expected, check that there are no loose or shorted leads in the wiring path.
- Verify that the sensor measurements are not being affected by electromagnetic interference (EMI). A test is to turn on/off-the potential sources of EMI and track the sensor results.
- If temperature indicated is decreasing, check for reversed polarity of thermocouple(s) / correct polarity (type “K”) is yellow (+) and red (-).
- Temperature shown is extremely high (2500oF+) likely indicates a failed thermocouple / Check for loose wiring / Replace thermocouple
No temperature is indicated
- Verify the cable connection of the thermocouple to the PLC controller has not been crimped, damaged, or loosened.
Heater wiring terminal burned off
- Steel or brass screw used / Replace with stainless steel screw and nut
- Wire strands missing at terminal / Re-strip and terminate wire
- Loose terminal / Replace components and tighten
- For shortwave heaters check that cooling blowers are functional / Replace as needed.
Multiple heaters not functioning
- Broken heater / Measure resistance of heaters and replace if necessary with power OFF.
- Loose heater wires at terminal blocks / Check and tighten wiring with power OFF.
- Heater section fuse blown / Check for shorts to ground / Replace fuse
- SCR or SSR open/short circuit / replace SCR or SSR.
- Bad thermocouple / replace as required.
One heater not functioning
- Broken heater / Measure resistance of heater and replace if necessary, with power OFF. Broken heater will be an open circuit.
Equipment won’t start
- E-Stop Active / Check for E-stop buttons or pull cables in tripped position & reset
- Overtemperature Alarm Active / Check for over-temp condition / Reset device
- Output Power not Enabled / Press Output Power Enable button on control panel
- Door Open or Limit Switches not Functioning / Some equipment has doors that must be closed for equipment to operate, check that all doors are properly closed and latched and all limit switches activated / Replace limit switches if needed